| Implementation of the standards: | | |
| 1) This product is designed and manufactured according to GB/T12706-2002. | |
| 2) flame retardant power cable accordance with the standards of production enterprises, | |
| flame retardant characteristics meet the requirements GB/T18380.3. | |
| 3) fire-resistant power cables manufactured according TO corporate standards, | |
| including fire-resistant characteristics meet GB/T12666.6 requirements. | |
| characteristic | | |
| 1) Long-term allowable working temperature of cable conductor does not exceed 70 ℃. | |
| Circuit is blocked(the longest duration of no more than 5 seconds), | |
| The conductor temperature does not exceed 160 ℃; | |
| 2) While installation the ambient temperature should not be less than 0 ℃, | |
| lower than 0 ℃ should be preheated. | | |
| Minimum bending radius of not less than cable diameter, single-core cables without armor 20 times, | |
| There with armor-cable 15 times.Three-core cables without armor 15 times, There with armor-cable 12 times |
| 3) DC resistance of conductor shall comply with the provisions of GB/T3956. | |
| 4) Power frequency withstand voltage test: 3.5kV/5min without breakdown. | |
| main use | | |
| This product is suitable for AC rated voltage 0.6/1kV the circuit,Transmission of electrical energy used. |
| Flame retardant power cable is suitable Installed in fire-retardant demanding situations. | |
| Resistant power cable for high-rise buildings, shopping malls and other densely populated areas. | |
| Retardant performance: | | |
| 1) Retardant cable can withstand GB/T18380.3 prescribed bunched burning test, | |
| 2)Smoke density in accordance with the requirements of GB/T17651.1, | |
| 3)Combustion gases precipitated HCL content should be ≤ 100mg / g. | |
| 4)resistant cable can withstand GBA/T12666.6 fire test requirements. | |